I te marama o Akuhata, ka haere nga kaitoi muri-hoko o HV Hipot ki Xiangyang.Ko te kaupapa o tenei haerenga he whakarato ratonga patuiro ngaohiko hihiko mo Xiangyang Power Supply Company.
I muri i te taenga ki te waahi, me te awhina me te mahi tahi a te kaihoko, ka mahia te whakaurunga o te hiko hiko hiko uira.
I runga-pae patuiro o GDCY-400kV uira hihiko ngaohiko generator
Te whakatikatika i te tawhiti o te poroporo i runga i te waahi: te whakatikatika i te tawhiti o te poi tinana me te whakatikatika i te tawhiti poroporo (3000/200/i ine)
I runga i te waahi whakamatautau-whakamatautau: 30KV pai me te kino polarity whakamatautau maha (tutaki T1=1.2±30%/T2=50±20%us/TC=2 ki te 6us)
Te whakamatautau kaha i runga i te waahi: ngaohiko whakatau 80% putanga
Te whakangungu ariā me te whakahaere i runga i te waahi:
Nga mahi a te Kaihoko - he whakamatautau hua whakamatautau: 10KV hiko hiko
1. Te whakamatautau ngaru katoa
Nga whakaritenga whakamatautau: ngaohiko whakamatautau 75KV, te wa ngaru T1=1.2±30%/T2=50±20%us
Mahi mara: te whakamahi i te putanga ngaohiko rua-waahi
Whakarerekenga ngaru i runga-pae:
Te ātete mahunga ngaru: 150Ω mo te taumata tuatahi, 500Ω mo te taumata tuarua (2 1KΩ whakarara)
Te ātete hiku ngaru: 1st stage 45Ω, 2nd stage 45Ω
Te mahi whakamatautau me te ahua ngaru:
2. Whakamātautau tapahi
Nga whakaritenga whakamatautau: ngaohiko whakamatautau 85KV, te wa mahunga ngaru T1=1.2±30%, te wa tapahi TC=2 ki te 6us
Mahi mara: te whakamahi i te putanga ngaohiko rua-waahi
Whakarerekenga ngaru i runga-pae:
Te ātete mahunga ngaru: Taumata 1 75Ω, Taumata 2 500Ω (2 1KΩ whakarara)
Te ātete hiku ngaru: 1st stage 45Ω, 2nd stage 45Ω
Te mahi whakamatautau me te ahua ngaru:
I muri i tenei raupapa whakangungu, he tino mohio te kaihoko ki te huinga katoa o nga taputapu, ka nui ake te maia o te kaihoko ki te mahi tonu!
Wā tuku: Akuhata-24-2022