Nga tikanga mo te ine i te ōwehenga whakauru
Ko te ōwehenga absorption me te taupū polarization o te transformer me te akomanga ngaohiko o 10kv me te kaha o te whakawhiti whatunga tohatoha i raro i te 4000kvA e kore e taea te ine.
A, no te te taumata ngaohiko transformer he 220kv ki runga ake ranei me te kaha kei runga ake i te 120MVA, me whakamahi te 5000V insulation resistance tester ki te ine i te ōwehenga absorption.Ko te ōwehenga absorption kaua e iti iho i te 1.5 i te pāmahana rūma.A, no te nui atu i te 10000MΩ i te R60min te uara parenga whakaraerae, kaore e hiahiatia te taurangi polarization.
GD3126A (GD3126B) Whakamatau Aatete Waiata 5kV/10TΩ (10kV/20TΩ)
Ko nga raruraru e whai ake nei me aro nui ki te ine i te taupae polarization ōwehenga absorption
(1) Ko ia inenga me whiriwhiri i te ngaohiko ngaohiko taumata whakamaarama parenga parenga, kaore he paanga o nga kaihanga rereke;
(2) I te wa o te ine, me whiriwhiri te raina whakaputa ngaohiko teitei hei raina whakamarumaru ngaohiko teitei motuhake, kaore e taea te whakawhiti i te raina whakaputa L me N, kaua e werohia te raina whakamatautau me te aukati i te wa e taea ai;
(3) Kia kore ai te toenga o te utu e pa ki nga hua o te whakamatautau, me whakakore katoa te matū i whakamatauria i mua i te whakamatautau;
(4) I mua i te whakamatautau, tangohia te waea whakamatautau, horoia te hononga whakamatautau kia ma me te whakarite kia pono te whenua;
(5) Ki te aukati i te awe o naianei leakage mata tae noa ki taea i roto i te haumākū rangi he whakamātautau iti, ka tika ki te hono i te mowhiti whakangungu rakau;
Ko nga raruraru i runga ake nei me aro ki te ine i te taurangi polarization ōwehenga absorption.He mea tika kia aro ki te kowhiringa o te ngaohiko mo nga taputapu hiko.Me rite ki nga whakaritenga whakamatautau.
Te wa tuku: Hanuere-10-2023